Precautions for stainless steel storage tanks

       1, Stainless steel storage tank area fire and explosion protection should be in accordance with regulations. Low-expansion air foam fire extinguishing systems should be in accordance with regulations.
       2, should be kept clean and tidy, and there should be no dry grass, no oil stains, and no flammable materials in the fire dike.
       3, The drainage system should be equipped with water sealing wells; the drainage pipes should be equipped with valves outside the fire embankment; when the oil tank is drained, there should be a dedicated person to monitor and promptly clean up the residual oil in the water sealing wells.
       4,stainless steel storage tankNon-explosion-proof electrical equipment and high-voltage overhead lines should not be installed in the area.
       5,Fire embankments should be set up in accordance with regulations and should be kept intact.
       6,The top of the tank should be free of oil and water. Oil storage tank inlet and outlet pipelines,Valves should be insulated.
       7,Light hole in the top of the tank,Gauge hole cover,The gasket should be kept intact and the hole cover should be tightly closed. The dipstick should be equipped with a non-sparking metal gasket.
       8,breathing valve,The base of the hydraulic safety valve should be equipped with a flame arrester. Flame arresters should be inspected at least quarterly1Second-rate.
       9,The inlet and outlet oil pipelines should be equipped with flexible hose compensators.
       10,The tank should be equipped with a lightning protection and anti-static grounding device, and its grounding resistance should not be greater than10Ω. The grounding point is along the bottom edge of the tank.30mSet up at least one grounding location, and there should be no less than two grounding locations for a single tank.
       11,The lightning protection and anti-static grounding device should be inspected as a whole every spring, and the grounding resistance value should meet the requirements.
       12,stainless steel storage tankBetween the pontoon and the tank wall, two rods with a cross-sectional area of ​​not less than25mm2soft copper wire connection.
       13,The oil content should be within the safe tank level.
       14,When the condensate oil level is higher than the heating coil, the steam riser should be used to heat it first. After the condensate oil melts, the steam coil should be used for heating.
       15,Chemical fiber clothing and shoes with nails should not be worn on the tank. The top of the tank should not be opened,Turn off non-explosion-proof flashlight.
       16,stainless steel storage tankOil pipeline fire in area,Tank cleaning operations should comply with industry regulations.
       17,If the equipment catches fire, it should be reported promptly and all operations should be stopped. Organize firefighting and initiate emergency plans in a timely manner.